Fire Sleeve – Ducting
Overview
Fire Sleeves prevent the spread of fire where plastic pipes or plastic ducts penetrate fire compartment walls.
Features & Benefits
- Tested to BSEN 1366-3: 2009
- Tested with Uncapped/Uncapped (U/U) duct configurations as required for ventilation ducts
- Up to 2 hour fire rating
- Suitable for masonry walls or plasterboard partitions
- Suitable for insulated and non-insulated partitions
- Can be retrofitted
- No mechanical fixings required
- Robust galvanised steel shell
- Performance unaffected by weathering (Type X Durability)
Technical Information
Technical Information
Regulations
Building Regulations impose limitations on all pipes passing through fire compartment walls and floors. QRS Intumescent Fire Sleeves allow plastic ducts to meet the requirements of the Building Regulations. QRS Intumescent Fire Sleeves have been tested according to BSEN 1366-3: 2009 where various plastic duct sizes have met insulation and integrity criteria for this standard for up to 2 hours.
Composition
The QRS Intumescent Fire Sleeves consist of a flexible galvanised steel shell containing graphite based intumescent material.
They are manufactured to suit flat ducts of 110x54mm, 204x60mm, and 220x90mm. And round ducts with 100mm and 125mm overall diameter.
Durability
Tested to Type X durability which means the QRS Fire Sleeves can be installed in conditions exposed to weathering. QRS CE/UKCA Marked Fire Sleeves are expected to last the lifetime of the building.
Applications/Installation
The QRS Intumescent Fire Sleeve should be placed around the ventilation duct, positioned centrally within the partition and should be flush or protrude from each face of the wall. The plasterboard should be cut to a tight fit around the QRS Intumescent Fire Sleeve, and any gaps should be sealed with the Quelstop Intumescent Acrylic Sealant, part number QSS310.
For all sleeve types, please refer to manufacturers installation guidance prior to system design or installation.
Performance
Product Code | Duct Size (mm) | Space needed around duct to fit QRS Sleeve (mm) | Recommended aperture (mm) |
QRS length (mm) |
Fire Rating |
QRS110/54 | 110 x 54 | 9 | 130 x 73 | 140 | 120 minutes |
QRS205/60 | 204 x 60 | 9 | 225 x 80 | 180 | 120 minutes |
QRS220/90 | 220 x 90 | 18 | 256 x 126 | 140 | 120 minutes |
QRS110* | 100 | 10 | 130 | 180 | 120 minutes |
QRS130* | 125 | 20 | 170 | 180 | 90 minutes |
QRS 75 | 75 Semi rigid | 8 | 90 | 140 | 120 minutes |
QRS 90* | 90 Semi Rigid | 13 | 116 | 140 | 120 minutes |
* QRS110, QRS130 and QRS 90 are not currently CE Marked
Documentation
Resources
Manuals and Documentation
Fitting Instructions - Fire Sleeve
URL for Fitting Instructions - Fire Sleeve copied to clipboard.
Fire Sleeve - CE Marked Material Safety Data Sheet (COSHH)
URL for Fire Sleeve - CE Marked Material Safety Data Sheet (COSHH) copied to clipboard.
Fire Sleeve - Plastic Vent Ducts Product Data Sheet
URL for Fire Sleeve - Plastic Vent Ducts Product Data Sheet copied to clipboard.
Fire Sleeve - Declaration of Performance
URL for Fire Sleeve - Declaration of Performance copied to clipboard.
Catalogues
Ventilation Systems Catalogue
URL for Ventilation Systems Catalogue copied to clipboard.
Ducting Range - VS Catalogue Pages
URL for Ducting Range - VS Catalogue Pages copied to clipboard.
Fire Sleeve - Catalogue Page
URL for Fire Sleeve - Catalogue Page copied to clipboard.
Certificate
Fire Sleeve - Certificate of Constancy of Performance
URL for Fire Sleeve - Certificate of Constancy of Performance copied to clipboard.
Reports
Chiltern Report (RF11067)
URL for Chiltern Report (RF11067) copied to clipboard.
Chiltern Report (BMT/FEI/F13139)
URL for Chiltern Report (BMT/FEI/F13139) copied to clipboard.
Chilton Report (BMTFEIF13139)
URL for Chilton Report (BMTFEIF13139) copied to clipboard.
Warrington Report (360670 Issue 2)
URL for Warrington Report (360670 Issue 2) copied to clipboard.